Answer to Question 15.

3. How are the output fuse/mcb rating calculated and how does ripple affect the calculation?

The output fuse rating is found by multiplying the charger output current by 2 on standard chargers (20% PK-PK ripple voltage) or 1.2 on smoothed chargers (ripple 1% PK-PK or less).